Heat-sensitive cable that detects fire at any point along its length — for cable trays, conveyors, tanks, tunnels and hazardous areas. Works with any fire alarm panel, and is supplied, installed and commissioned by our engineers in Qatar.
Two steel conductors in heat-sensitive polymer. At the rated temperature the polymer melts, the conductors short and the adapter unit sends a fire signal to the panel — at any point along the cable.
Approvals shown are for the 68–138 °C ratings. 180 °C cables carry CE and EAC (plus FM on the conventional type). The 230 °C CR/OD cable has no listed approval.
Pick the rating above the highest normal temperature in the area. The cable must not sit above its maximum ambient temperature.
| Rating | Alarm tolerance (UL / FM) | Max. ambient temperature | Cable types | Response, flame test |
|---|---|---|---|---|
| 68 °C | ±4.15 °C / ±5 °C | 45 °C | Conventional, CR/OD, EP | 7–8 s |
| 88 °C | ±4.15 °C / ±5 °C | 60 °C | Conventional, CR/OD, EP | 8–10 s |
| 105 °C | ±4.15 °C / ±5 °C | 75 °C | Conventional, CR/OD, EP | 8–10 s |
| 138 °C | ±5.55 °C / ±5 °C | 93 °C | Conventional, CR/OD, EP | 9–11 s |
| 180 °C | ±5.55 °C / ±5 °C | 121 °C | Conventional, CR/OD, EP | 14–16 s |
| 230 °C | ±8 °C / ±5 °C | 160 °C | CR/OD only | 20–22 s |
Response time: cable placed directly in an alcohol lamp flame, from the manufacturer’s test data.
Each zone needs one adapter unit at the panel end and one termination unit at the far end of the cable.
| Conductors | 2 × 0.9 mm galvanized steel wire |
| Cable diameter | 4 mm (EP: 4.9 mm) |
| Protection | IP68 |
| Service life | 12 years |
| Length | 500 m standard, 1000 m maximum |
| Min. bending radius | 150 mm |
| Loop resistance | 0.64 ± 0.1 Ω/m |
| Insulation resistance | ≥ 500 MΩ at 500 VDC |
| Installation temperature | ≥ −10 °C (CR/OD: ≥ −30 °C) |
| Weight | 0.021 kg/m (EP: 0.038 kg/m) |
| Flame retardant | UL94 V-0, IEC 60332-2 |
| Detection distance | ≤ 500 m |
| Supply (adapter) | 24 VDC (UL 16–26 VDC, FM 16–28 VDC) |
| Termination unit | No power needed |
| Current (adapter) | Standby ≤ 20 mA, fire ≤ 35 mA, fault ≤ 25 mA |
| Environment | −45 °C to +60 °C, up to 95% RH |
| Protection | IP66 |
| Housing | Aluminium alloy, 127 × 85 × 58 mm |
| Weight | MS1000-I 0.37 kg, MS1000-P 0.33 kg |
| Ex marking (P Ex) | II 2G Ex ib IIC T6 Gb, II 2D Ex ib IIIC T85 °C |
Linear heat cable suits long, harsh or hard-to-reach areas where point detectors are not practical.
Tell us the products and quantities you need. We will come back with price, availability and delivery time.
P.T.S is a brand of P.T.Security Technology Co., Ltd. Specifications are taken from the manufacturer’s datasheets and may change without notice.