Stairwell Pressurization Test

On-site testing of stair pressurization systems to NFPA 92. We measure the pressure difference and door opening force at every stair door, check the fans start on fire alarm, and document the results floor by floor.

AT A GLANCE
Standards
NFPA 92 · NFPA 101
Systems
Stair and lobby pressurization fans
Pressure
Pressure difference at every stair door
Door force
Opening force at every stair door
Deliverable
Floor-by-floor test report
WHAT IS STAIR PRESSURIZATION?

Keeping smoke out of the escape stairs

A stair pressurization system uses fans to blow fresh outdoor air into the escape stairwell when the fire alarm operates. The higher pressure inside the stair stops smoke on the fire floor from leaking in, so people can escape and firefighters can use the stair safely.

The pressure must be high enough to hold smoke back, but not so high that people cannot open the stair doors. Testing proves both, floor by floor — before Civil Defence inspection and at regular intervals after handover.

What you receive
  • Pressure difference readings across every stair door, with all doors closed
  • Door opening force measured at each stair door with the fans running
  • Pressure readings repeated with the design number of doors open, as per NFPA 92
  • Check of fan start on fire alarm, standby fan, dampers and cause and effect
  • Floor-by-floor test report for your Civil Defence records
Pressure & door force test

With the fans running and all stair doors closed, our engineers check every floor:

  • Pressure difference between the stair and each floor
  • At least 12.5 Pa in sprinklered buildings under NFPA 92, with higher values for unsprinklered buildings
  • Door opening force at each stair door — no more than 133 N (30 lbf) under NFPA 101
  • Fan speed, airflow and relief damper operation
  • Any floor or door outside the limits flagged for adjustment
System function test

We test the full sequence from the fire alarm: the fans must start automatically, build up pressure and hold it as doors open and close. We check fan run and fault signals, standby fans, motorized and relief dampers, and the manual controls.

As per NFPA 92, we also repeat the pressure readings with the design number of stair doors open, to prove the system still holds smoke back during evacuation. Results are written up floor by floor, with the adjustments needed for the system to pass Civil Defence inspection.

MORE SPECIALIST TESTS

Other tests we carry out in-house

FM-200 Room Integrity Test
Door-fan testing that proves your enclosure holds the clean agent for the full retention time.
View test →
Foam Conductivity Test
Confirms your AFFF proportioning delivers the correct 3% or 6% concentration.
View test →
Fire Pump Performance Test
Churn and annual flow testing of electric and diesel fire pumps to NFPA 25.
View test →
Need this test carried out?
Our engineers can schedule a visit anywhere in Qatar — 24/7 for urgent cases.
Call +974 7070 8830WhatsApp
BOOK A TEST

Book your test with our engineers

Tell us about the system and location. We will confirm the scope, schedule and price.

Office
Building 194, Street 105, Zone 57, Doha, Qatar
Availability
24/7 emergency response, 365 days a year
Chat on WhatsApp