Foam System Conductivity Test

Conductivity testing of AFFF foam solution that confirms your proportioning system delivers the correct 3% or 6% concentration — so the foam suppresses the fire as designed.

AT A GLANCE
Foam type
AFFF 3% and 6%
Method
Conductivity, against a calibration curve
Sampling
3 discharge samples at 20, 40 & 60 s
Reference
NFPA 11
Deliverable
Test report with readings & result
WHY IT MATTERS

The right foam concentration puts the fire out

A foam system relies on its proportioner injecting exactly the right amount of concentrate into the water stream. Too little produces weak, unstable foam that breaks down on the fire; too much wastes expensive concentrate and shortens the system’s discharge time.

Fire Cloud carries out conductivity testing for AFFF foam systems at 3% and 6% concentration, confirming that the foam-to-water ratio discharged by your system stays within the required range.

Foam solution samples in graduated measuring cylindersFoam bladder tank with ratio proportioner
What you receive
  • On-site calibration with your own water and foam concentrate
  • Live discharge sampling at 20, 40 and 60 seconds
  • Test report with conductivity readings and the calculated concentration
  • Clear pass / fail result and recommendations if adjustment is needed
  • Testing for deluge, bladder-tank and foam-water systems
TEST PROCEDURE

How the conductivity test works

  1. Prepare reference samplesThree graduated bottles are filled with 100 ml of the same water that supplies the deluge system and foam bladder tank.
  2. Add foam concentrate2, 3 and 4 ml of water are removed and replaced with 2, 3 and 4 ml of foam concentrate.
  3. Build the calibration curveEach sample is mixed thoroughly, its conductivity measured with a calibrated meter, and the readings recorded.
  4. Live foam dischargeThe system is discharged and three samples are taken — after 20, 40 and 60 seconds.
  5. Compare the resultsThe average of the three discharge readings is compared with the calibration samples.
  6. Confirm the concentrationFor a 3% system, the result must fall between 3% and 4% — confirming the discharge is at the correct concentration to suppress the fire.
Foam system due for its annual test?

We test, report and — if the proportioning is out of range — help you correct it, so your system is ready for inspection.

Book a test
MORE SPECIALIST TESTS

Other tests we carry out in-house

FM-200 Room Integrity Test
Door-fan testing that proves your enclosure holds the clean agent for the full retention time.
View test →
Clean Agent Cylinder Refilling
FM-200 and Novec 1230 cylinder repair, refill and 24-hour emergency recharge.
View test →
Fire Pump Performance Test
Churn and annual flow testing to NFPA 25 with a documented pump curve.
View test →
Need this test carried out?
Our engineers can schedule a visit anywhere in Qatar — 24/7 for urgent cases.
Call +974 7070 8830WhatsApp
BOOK A TEST

Book your test with our engineers

Tell us about the system and location. We will confirm the scope, schedule and price.

Office
Building 194, Street 105, Zone 57, Doha, Qatar
Availability
24/7 emergency response, 365 days a year
Chat on WhatsApp