Doha, Qatar +974 7070 8830 khaled@firecloud360.com
24/7 emergency response, 365 days a year
TRADING, CONTRACTING
& SERVICES
Request a Quote
PRODUCTS · LINEAR HEAT DETECTION

P.T.S MS1000 digital linear heat detector

Heat-sensitive cable that detects fire at any point along its length — for cable trays, conveyors, tanks, tunnels and hazardous areas. Works with any fire alarm panel, and is supplied, installed and commissioned by our engineers in Qatar.

LINEAR HEAT DETECTOR AT A GLANCE
Cable types
Conventional, CR/OD outdoor & chemical, EP anti-EMI & explosion-proof
Alarm ratings
68, 88, 105, 138, 180 and 230 °C
Approvals
FM · UL · CE · EAC; ATEX & IECEx Ex unit
Zone length
Up to 500 m of cable per adapter unit
Support
Design, installation, testing and Civil Defence commissioning
LINEAR HEAT CABLE

MS1000 digital linear heat cable

Two steel conductors in heat-sensitive polymer. At the rated temperature the polymer melts, the conductors short and the adapter unit sends a fire signal to the panel — at any point along the cable.

P.T.S MS1000 conventional linear heat detection cable with red PVC outer jacket, cutaway view
MS1000FMULCEEAC
MS1000 Conventional Linear Heat Cable
  • Alarm ratings: 68, 88, 105, 138 and 180 °C
  • PVC outer jacket, 4 mm cable, IP68 — for general indoor and industrial use
  • 500 m standard reel, 1000 m maximum length; 12-year service life
Ask for price →
P.T.S MS1000 CR/OD outdoor and chemical resistant linear heat cable with black fluoroplastic jacket, cutaway view
MS1000 CR/ODULCEEAC
MS1000 CR/OD Outdoor & Chemical Resistant Cable
  • Alarm ratings: 68, 88, 105, 138, 180 and 230 °C
  • Fluoroplastic (FEP) jacket — UV, weather, acid, alkali and salt-spray resistant
  • Low smoke, halogen-free and non-combustible; installs down to −30 °C
Ask for price →
P.T.S MS1000 EP anti-EMI and explosion-proof linear heat cable with metal woven mesh, cutaway view
MS1000 EPULCEEAC
MS1000 EP Anti-EMI & Explosion-Proof Cable
  • Alarm ratings: 68, 88, 105, 138 and 180 °C
  • Woven metal mesh over the jacket stops electrical interference (EMI)
  • For hazardous areas with the MS1000-P (Ex) ATEX termination unit; 4.9 mm cable
Ask for price →

Approvals shown are for the 68–138 °C ratings. 180 °C cables carry CE and EAC (plus FM on the conventional type). The 230 °C CR/OD cable has no listed approval.

CHOOSE THE ALARM TEMPERATURE

Alarm temperature ratings

Pick the rating above the highest normal temperature in the area. The cable must not sit above its maximum ambient temperature.

RatingAlarm tolerance (UL / FM)Max. ambient temperatureCable typesResponse, flame test
68 °C±4.15 °C / ±5 °C45 °CConventional, CR/OD, EP7–8 s
88 °C±4.15 °C / ±5 °C60 °CConventional, CR/OD, EP8–10 s
105 °C±4.15 °C / ±5 °C75 °CConventional, CR/OD, EP8–10 s
138 °C±5.55 °C / ±5 °C93 °CConventional, CR/OD, EP9–11 s
180 °C±5.55 °C / ±5 °C121 °CConventional, CR/OD, EP14–16 s
230 °C±8 °C / ±5 °C160 °CCR/OD only20–22 s

Response time: cable placed directly in an alcohol lamp flame, from the manufacturer’s test data.

ADAPTER & TERMINATION UNITS

Adapter and termination units

Each zone needs one adapter unit at the panel end and one termination unit at the far end of the cable.

P.T.S MS1000-I linear heat detector adapter unit with run, fire and fault LEDs
MS1000-IFMULCEEAC
MS1000-I Adapter Unit
  • Connects the heat cable to any fire alarm panel input or zone
  • 24 VDC; standby ≤20 mA, fire ≤35 mA, fault ≤25 mA
  • Run, fire and fault LEDs; up to 500 m of cable per unit
Ask for price →
P.T.S MS1000-P linear heat detector termination unit with fire test and fault test buttons
MS1000-PFMULCEEAC
MS1000-P Termination Unit
  • End-of-line unit for conventional and CR/OD cable (and EP in safe areas)
  • Fire test and fault test buttons for easy commissioning
  • No power needed; IP66 aluminium alloy housing, 127 × 85 × 58 mm
Ask for price →
P.T.S MS1000-P (Ex) ATEX explosion-proof termination unit
MS1000-P (Ex)ATEXIECExFMCEEAC
MS1000-P (Ex) Explosion-Proof Termination Unit
  • End-of-line unit for MS1000 EP cable in hazardous areas
  • II 2G Ex ib IIC T6 Gb · II 2D Ex ib IIIC T85 °C
  • Use with EP cable rated 68–180 °C; IP66 housing
Ask for price →
TECHNICAL DATA

Cable and unit specifications

Linear heat cable
Conductors2 × 0.9 mm galvanized steel wire
Cable diameter4 mm (EP: 4.9 mm)
ProtectionIP68
Service life12 years
Length500 m standard, 1000 m maximum
Min. bending radius150 mm
Loop resistance0.64 ± 0.1 Ω/m
Insulation resistance≥ 500 MΩ at 500 VDC
Installation temperature≥ −10 °C (CR/OD: ≥ −30 °C)
Weight0.021 kg/m (EP: 0.038 kg/m)
Flame retardantUL94 V-0, IEC 60332-2
Adapter & termination units
Detection distance≤ 500 m
Supply (adapter)24 VDC (UL 16–26 VDC, FM 16–28 VDC)
Termination unitNo power needed
Current (adapter)Standby ≤ 20 mA, fire ≤ 35 mA, fault ≤ 25 mA
Environment−45 °C to +60 °C, up to 95% RH
ProtectionIP66
HousingAluminium alloy, 127 × 85 × 58 mm
WeightMS1000-I 0.37 kg, MS1000-P 0.33 kg
Ex marking (P Ex)II 2G Ex ib IIC T6 Gb, II 2D Ex ib IIIC T85 °C
APPLICATIONS

Where linear heat detection is used

Linear heat cable suits long, harsh or hard-to-reach areas where point detectors are not practical.

Cable trays & trenches
Power and control cables in plants, substations, basements and service shafts.
Transformers & switchgear
Transformers, control cabinets and power distribution equipment.
Conveyors
Coal, mining and industrial conveyor belts.
Tanks & petrochemical
Floating-roof and dome-roof tanks, spherical tanks, pipelines and reactors.
Tunnels
Road, metro and utility tunnels, including cable tunnels and tunnel ceilings.
Warehouses & racking
In-rack detection for high-bay storage and logistics buildings.
Power & industry
Power plants, cooling towers, PV systems, steel plants and offshore platforms.
Airports & hangars
Passenger channels, baggage carousels and aircraft hangars.
ALSO FROM FIRE CLOUD

Services for your linear heat detection

Fire alarm & detection
Design and installation of linear heat detection zones and their connection to your fire alarm panel.
View service →
Fire alarm panel programming
Zone, cause-and-effect and output programming for LHD zones, on site or remote.
View service →
Maintenance & AMC
Periodic testing of linear heat zones with the termination unit fire and fault test, under an annual contract.
View service →
Need a price for your project?
Send us your device list or drawings — we will come back with price, availability and delivery time.
Call +974 7070 8830WhatsApp
ASK FOR A PRICE

Send us your device list

Tell us the products and quantities you need. We will come back with price, availability and delivery time.

Office
Building 194, Street 105, Zone 57, Doha, Qatar
Availability
24/7 emergency response, 365 days a year
Chat on WhatsApp







    P.T.S is a brand of P.T.Security Technology Co., Ltd. Specifications are taken from the manufacturer’s datasheets and may change without notice.